Warning
titleCAUTION

Electro-magnetic discharge (lightning) damage is not covered under warranty. The recommendations in this document, when followed correctly, give the user the best protection from the harmful effects of EMD. However 100% protection is neither implied nor possible.

Grounding and lightning protection recommendations

  • The wireless device should be placed on the pole at a height that is at least 1 meter below the top of the pole. In this case, there is a significant probability that the lightning strikes the pole and not the wireless device. The pole should be properly grounded: connected to the building lightning protection circuit according to your local regulations.
  •  All equipment must be connected at stabilized and surge protected power sources which must be properly grounded.
  • The end of the FTP service cable that is connected to the power supply should be assembled with a shielded RJ-45 connector. The other end of the FTP service cable (connected to the wireless device) should be assembled with unshielded (standard) RJ-45 connector.
  • The power supply is grounded via a three-conductor power cord and a grounded socket.
  • AUX-ODU-LPU-L, AUX-ODU-LPU-G and wireless device grounding is performed using grounding bolt.
  • Antenna pole and wireless device should be connected to the common ground ring. Grounding cables should be no less than 10AWG thick and must use corrosion-resistant connectors.

Requirements to the lightning protection unit AUX-ODU-LPU-L location

Include Page
Grounding for AUX-ODU-LPU-L
Grounding for AUX-ODU-LPU-L

Requirements to the lightning protection unit AUX-ODU-LPU-G location

Include Page
Grounding for AUX-ODU-LPU-G_new
Grounding for AUX-ODU-LPU-G_new